How to use this calculator
- Enter the load in watts, or enter amps directly.
- Enter the supply voltage (120 or 240 V in the US).
- Say whether the load is continuous (runs 3 hours or more).
- Read the breaker size and the matching minimum wire.
The 125 percent rule
Breakers and wires are rated for continuous loads at 80 percent of their rating, which is the same as sizing the circuit at 125 percent of the load. An EV charger that draws 32 A continuously needs a 40 A circuit, for example.
After finding the current (watts divided by volts), multiply by 1.25 for a continuous load and round up to the next standard breaker size. The wire must then be rated for at least that breaker, within code limits.
Frequently asked questions
What size breaker for a 7.2 kW EV charger?
At 240 V that is 30 A. As a continuous load it needs 37.5 A, so a 40 A breaker with 8 AWG copper wire is the usual choice.
What is the 125 percent rule?
A continuous load must not exceed 80 percent of the breaker rating, so you size the breaker at 125 percent of the load current.
Can I use a bigger breaker than the wire allows?
No. The breaker protects the wire, so it must not be larger than the wire ampacity allows.
Does this cover motors?
No. Motor circuits follow separate rules for starting current and overload protection.