Like ToolFern? Prefer us as your source on Google →

Wire Size & Voltage Drop Calculator

Enter the current, one-way cable length and voltage to find the smallest AWG wire that carries the load and keeps voltage drop under your limit.

-
Recommended wire size
-
Ampacity (75 C)
-
Voltage drop (V)
-
Voltage drop (%)

Ampacity values assume 75 C insulation and a small number of conductors. Temperature, conduit fill, long runs and local code can require a larger wire. Have an electrician confirm any installation.

Voltage drop = 2 x length x current x resistance per 1000 ft / 1000 (single phase or DC), or 1.732 x length x current x resistance / 1000 (three phase). Resistance values are for copper at about 75 C; aluminum is about 1.64 times higher.

How to use this calculator

  1. Enter the load current in amps (use the Watts to Amps Calculator if you only know watts).
  2. Enter the one-way distance from the source to the load in feet.
  3. Pick copper or aluminum, the system type and the voltage drop you will accept (3 percent is common for branch circuits).
  4. Read the smallest wire size that passes both the ampacity and the voltage drop test.

How wire size is chosen

A wire has to pass two tests. First, its ampacity must be at least the load current, and 125 percent of it for a continuous load. Second, the voltage lost along the wire (current times resistance, out and back) must stay under your limit, commonly 3 percent for a branch circuit and 5 percent in total.

Long runs and low voltages such as 12 V solar and battery cables fail the voltage drop test long before the ampacity test, which is why they need much thicker wire. This calculator checks both and picks the first standard AWG size that passes.

Frequently asked questions

What wire size do I need for 30 amps?

For 30 A of continuous load the wire must carry 37.5 A, so 8 AWG copper (50 A at 75 C) is the usual minimum, and a long run may need 6 AWG or larger to keep voltage drop low.

What voltage drop is acceptable?

A common guideline is 3 percent or less on a branch circuit and 5 percent or less from the service to the farthest load. Low-voltage DC systems are often designed for 1 to 2 percent.

Is aluminum wire the same size as copper?

No. Aluminum has higher resistance and lower ampacity, so you need about one to two sizes larger than copper for the same load.

Does this replace the electrical code?

No. It is a planning estimate. The code and your inspector decide the wire, breaker and installation method.

Found this useful? Share it